Electrical connection

Damage to the unit due to a short circuit if water enters the electronics compartment.

  1. Ensure correct, tight line feedthrough through the cable feedthrough and membrane grommet with slot.

Danger of injury due to sharp edges on sheet metal/break-outs in the housing or in the electronics compartment.

Wear protective gloves if necessary. Carefully guide connecting cables into unit. Do not damage cables.

If the connecting cables are too short, the electronic slide-in module cannot be fully pulled out and fitted on the housing. Ensure connection cables of a sufficient length inside the ventilation unit.

A fixed wiring for the mains connection is mandatory. The power cable is already wired inside the unit and led out of the unit.

Take electronic unit with main board out of ventilation unit and attach as described below.

  1. Loosen the two quick-release locks and remove the front cover.
  2. Loosen both screws of the electronic slide-in module → arrows.
  3. 1

    Electronic slide-in module

  4. Pull out the electronic slide-in module and hook it into both recesses → arrows.
  5. Install optional additional circuit board(s) ZP 1 and/or ZP 2 in the slots and connect with the provided connection cables. Check DIP switch settings and adjust if necessary. For electrical connection and DIP switch settings → installation instructions of the accessories.
  6. Plug optional KNX or EnOcean plug-in module (K-SM or E-SM) into slot X01 of the main board →installation instructions of the accessories.
  7. 1

    Cable feedthrough

    2

    Main switch

    3

    Cable feedthrough

    4

    Membrane grommet with slot

  8. Guide connection cables of the control units and additional components through cable feedthroughs [3] or [4] into ventilation unit. Ensure seal integrity (IP protection).
  9. Make electrical connections according to wiring diagram. For connection variants of the additional components → installation instructions of the accessories.
  10. Insert the electronic slide-in module into the electronics compartment and screw it in place with both screws.
  11. Attach front cover and secure with both quick-release clips.
  12. Set the main switch to On (position I). The LEDs on the RLS 1 WR switch on.
  13. Carry out a function test and put the ventilation unit into operation → Commissioning.
  14. Install control unit(s) → Wiring diagrams.